Robust Droop Controller for Accurate Proportional Load Sharing Among Inverters Operated in Parallel

Loughborough University · University of Sheffield

Indexed incrossref

Abstract

In this paper, the inherent limitations of the conventional droop control scheme are revealed. It has been proven that parallel-operated inverters should have the same per-unit impedance in order for them to share the load accurately in proportion to their power ratings when the conventional droop control scheme is adopted. The droop controllers should also generate the same voltage set-point for the inverters. Both conditions are difficult to meet in practice, which results in errors in proportional load sharing. An improved droop controller is then proposed to achieve accurate proportional load sharing without meeting these two requirements and to reduce the load voltage drop due to the load effect and the…