Abstract

The paper proposes several concepts of integrators for sinusoidal signals. Parallel and series associations of the basic PI units using the stationary frame generalized integrators are used for current control of active power filters. Zero steady state error for the concerned current harmonics are realized, with reduced computation, under unbalanced utility or load conditions. Designing of the PI constants, digital realization of the generalized integrators, as well as compensation of the computation delay etc. are studied. Extensive test results from a 10 kW active power filter prototype are demonstrated.