Output Impedance Design of Parallel-Connected UPS Inverters With Wireless Load-Sharing Control
Elisava Barcelona School of Design and Engineering · Universitat Politècnica de Catalunya
Abstract
This paper deals with the design of the output impedance of uninterruptible power system (UPS) inverters with parallel-connection capability. In order to avoid the need for any communication among modules, the power-sharing control loops are based on the P/Q droop method. Since in these systems the power-sharing accuracy is highly sensitive to the inverters output impedance, novel control loops to achieve both stable output impedance and proper power balance are proposed. In this sense, a novel wireless controller is designed by using three nested loops: 1) the inner loop is performed by using feedback linearization control techniques, providing a good quality output voltage waveform; 2) the intermediate loop…
Citation impact
- FWCI
- 32.02
- Percentile
- 100%
- References
- 26
Authors
5- JMJosep M. GuerreroCorresponding
Elisava Barcelona School of Design and Engineering, Universitat Politècnica de Catalunya
- LGL. GarciadeVicuna
Universitat Politècnica de Catalunya
- JMJ. Matas
Universitat Politècnica de Catalunya
- MCMiguel Castilla
Universitat Politècnica de Catalunya
- JMJaume Miret
Universitat Politècnica de Catalunya
Topics & keywords
- Output impedance
- Control theory (sociology)
- Voltage droop
- Total harmonic distortion
- Input impedance
- Electrical impedance
- Impedance bridging
- Microgrid
- Affordable and clean energy